8.18

Short Circuit Protection

8.18.1

Type 1 Coordination

For Type 1 coordination either aM type fuses or Circuit breakers can be applied as shown in the tables below:

8.18.1.1

Type 1 Coordination with GE Circuit Breakers:

GE Circuit Breaker

Soft Starter
Rated Current

O/L

Breaking

Capacity

A

A

Frame Type

O/L Type

KA

8 16 FD63 LTMD

16 65

17 40 FD63 LTMD

40 65

31 50 FD63 LTMD

50 65

44 63 FD160 LTMD

63 65

58 80 FD160 LTMD

80 65

72 80 FE160 LTMD

80 65

85 125 FE160 SMR1-125 65

105 160 FE160 SMR1-160 65
145 160 FE160 LTMD

160 65

170 250 FE250 LTMD

250 65

210 250 FE250 LTMD

250 65

310 400 FG630 SMR1-400 65
390 400 FG400 SMR1-400 65
460 630 FG630 SMR1-630 65
580 630 FG630 SMR1-630 65
650 800 FK800 SMR1s-800 50
820 1250 FK1250 SMR1s-1250 50
950 1250 FK1250 SMR1s-1250 50

1100 1250 FK1250 SMR1s-1250 50
1400 1600 FK1600 SMR1s-1600 50


8.18.1.2

Type 1 Coordination with Type aM Siba Fuses:

SIBA aM Fuses

Soft Starter

Rated Current

Rated

Current

Breaking
Capacity

A A P/No.

Size

Un

Type

KA

8

16

20 477 08.16

000

690

aM

120

17

20

20 477 08.20

000

690

aM

120

31

35

20 477 08.35

000

690

aM

120

44

50

20 477 08.50

00

690

aM

120

58

80

20 209 08.80

00

690

aM

120

72

100

20 209 08.100

00

690

aM

120

85

125

20 209 08.125

00

690

aM

120

105

160

20 210 08.160

0

690

aM

120

145

200

20 211 08.200

1

690

aM

120

170

200

20 211 08.200

1

690

aM

120

210

250

20 211 08.250

1

690

aM

120

310

400

20 212 08.400

2

690

aM

120

390

500

20 213 08.500

3

690

aM

120

460

630

20 213 08.630

3

690

aM

120

580

800

20 225 08.800

4

690

aM

120

650

800

20 225 08.800

4

690

aM

120

820

1000

20 225 08.1000

4

690

aM

120

950 2x630

2x20

213

08.630

2x3

690

aM 120

1100 2x800

2x20

225

08.800

2x4

690

aM 120

1400 2x800

2x20

225

08.800

2x4

690

aM 120


8.18.2

Type 2 Coordination

For Type 2 coordination, use fuses for semiconductor protection to protect the ASTAT-XT from a short circuit.
Fuses for semiconductor protection give excellent results because they have low I²t values and high interruption
ratings.
Recommended fuse selection procedure:
Fuse rated voltage: Choose minimum fuse rated voltage which is above the rated voltage of the mains.
Fuse rated current: Select a fuse which is able to carry 8 times the rated ASTAT-XT current for 30 seconds (this is
double the maximum ASTAT-XT current for the maximum acceleration time).
Fuse I²t: Verify that the I²t value of the fuse is less than or equal to the I²t value of the thyristor in the ASTAT-XT as
shown in the table below.