19 transient protection, Application diagrams – GE Industrial Solutions ASTAT XT User Manual

Page 73

Advertising
background image

73

• Application diagrams

Soft Starter

Bussman Fuses DIN 43620

Rated Current

Rated

Current

Breaking

Capacity

A A

2

Sec A P/No.

Size

Un

Type

KA

8 400 40

170M3808D

1

690

H.S.D.I.

200

17 5000 63

170M3810D

1

690

H.S.D.I.

200

31 10000 125

170M3813D

1

690

H.S.D.I.

200

44 12000 160

170M3814D

1

690

H.S.D.I.

200

58 15000 160

170M3814D

1

690

H.S.D.I.

200

72 18000 200

170M3815D

1

690

H.S.D.I.

200

85 50000 250

170M3816D

1

690

H.S.D.I.

200

105 60000 315

170M3817D

1

690

H.S.D.I.

200

145 10000 315

170M3817D

1

690

H.S.D.I.

200

170 140000 400

170M3819D

1

690

H.S.D.I.

200

210 200000 500

170M4864D

1

690

H.S.D.I.

200

310 600000 500

170M4864D

1

690

H.S.D.I.

200

390 700000 800

170M5814D

2

690

H.S.D.I.

200

460 800000 900

170M6813D

3

690

H.S.D.I.

200

580 1200000 1000

170M6814D

3

690

H.S.D.I. 200

650 2000000

2x800

2x170M5814D

2x2

690

H.S.D.I. 200

820 2000000

2x800

2x170M5814D

2x2

690

H.S.D.I. 200

950 4500000

2x1000

2x170M5816D

2x2

690

H.S.D.I. 200

1100 4500000

2x1100

2x170M6892D

2x2

690

H.S.D.I. 200

1400 6500000

2x1400

2x170M8555D

2x3

690

H.S.D.I. 200



8.19

Transient Protection

Line transient voltages can cause a malfunction of the ASTAT-XT and damage to the thyristors. All ASTAT-XTs
incorporate Metal Oxide Varistors (MOV) to protect from normal line voltage spikes.