GE Industrial Solutions ASTAT XT User Manual

Page 91

Advertising
background image

91

Appendix A - MODBUS RTU Protocol


A.8. Parameter Settings (4X References)
Parameter settings include all parameters that can be set manually. These parameters determine the modes of
operation of the ASTAT-XT. They also set protections level. All parameters are word (two bytes) parameters. The
protocol supports both reading and modifying of (most of) these parameters.

All of these parameters must be set with care. Inappropriate settings of some parameters can result in damage to
both the motor and the ASTAT-XT.

The parameters have the following 4x references:
Note: Use function 3 to read the parameter settings.

Parameter

#

Range

Default


Main Settings
Starter

Current

1 8..1400

58

(Amp.)

Motor

Current

2 4..4000

58

(Amp.)

Line/Delta Configuration

3

0 (Line), 1(Inside Delta)

0 (Line)

Undercurrent_FLT

4

0..90

0 (% of Im)

Undercurrent_DLY

5

1..40

10 (Seconds)

O/C

JAM

Fault

6 100..850 400

(%

of

Im)

O/C JAM Delay

7

0..50

5 (0.5 Sec.)

Overload_Class

8 0-iec

10,

1-iec

20,

0-iec

10

2-nema 10, 3-nema 20,
4-nema 30

Overload_Protect

9 0-Disable, 1-Enable after EOR

1-Enabled

2-Enable

Undervoltage_FLT

10

120..600 300

(Volt)

UnderVoltage_DLY

11

1..10

5 (Seconds)

Overvoltage_FLT 12

150..750 480

(Volt)

Overvoltage_DLY

13

1..10

2 (Seconds)

Reserved

14..24


Start Settings
Soft Start Curve

25

0..10 (5..9 are reserved)

0 (Standard).

Kickstart

Time

26

0..10

(Tenth

Seconds)

0

(No

Pulse)

Starting

Voltage/Current 27

10..80

30

(%

of

full

voltage)

Current

Limit

28

100..700 400

(%

of

Im)

Ramp UP Time

29

1..90

10 (Seconds)

Max.

Start

Time

30

1..60

30

(Seconds)

Number of Starts

31

1..10 & (11 = OFF)

10

Duty

Cycle

Time 32

1..60

30

(Minutes)

Start_Lockout

33

1..60

15 (Minutes)

EOR

Relay

Delay 34

0..40

5

(Seconds)

Reserved

35..40


Stop Settings
Soft Stop Curve

41

0..10 (5..9 are for reserved)

0 (Standard)

Ramp

DOWN

Time

42

1..30

10

(Seconds)

End

Torque

43

0..10

0

(Minimum)

Reserved

44..48


DUAL Settings
Starting VOLT-2

49

10..80 %, 100-400

30

Current

Limit-2

50

100..700 300

%

of

Im

Ramp

UP-2

51

1..90

10

(Seconds)

Ramp

DOWN-2

52

1..30

10

(Seconds)

Motor

Current-2 53

5..1400

31

(Amp.)

Reserved

54..56