• Control Keypad

4.7.9

COMM. Parameters

42

– Page 8 – With the Modbus standard PCB

Function &

Default

Range

Unit

Description

COMM.Protocol
Modbus

Profibus/
Modbus/
DeviceNet

Sets ASTAT-XT’s communication PROTOCOL.
Operational when the Modbus communication PCB is installed.

Baud Rate
9600 (MODBUS)

1200,
2400,
4800,
9600

Sets

ASTAT-XT’s

Baud Rate

.

Parity Check
EVEN

EVEN,
ODD,
NO

Sets ASTAT-XT’s communication Parity Check.

Station Number
OFF

OFF,1 –
247

Sets ASTAT-XT’s communication Station Number.

S. Link Par. Set
Disabled

Enabled/
Disabled

Enables parameter modification via serial communication

Ser. Link Control
Disabled

Enabled/
Disabled

Enables start, stop, reset, etc. via serial communication

Store Settings
COMM. Parameters

Same

as

Store Settings Main Settings

on page 28.

Note:
After changing communication parameters and storing them,
control power must be switched OFF and ON to load the new
communication parameters.


4.7.10

Comm. Parameters

42

– Page 8 – With the Profibus optional PCB

Function &

Default

Range

Unit

Description

COMM. PROTOCOL
Profibus

Profibus/
Modbus/
DeviceNet

Sets ASTAT-XT’s communication protocol.
Operational when the optional communication PCB is
installed.

Baud Rate

AUTO (Profibus)

User can not change the Baud Rate value.
Max. rate is 12 mega bit per second (MBPS).

Parity Check
AUTO (Profibus)

User can not change the Parity Check value.

PROFI.Network ID
OFF

OFF, 1-126

Sets the Profibus network ID.
When set to OFF the Profibus card will not function.

S. Link Par. Set
Disabled

Enabled/
Disabled

Enables parameter modification via serial
communication

Ser. Link Control
Disabled

Enabled/
Disabled

Enables start, stop, reset, etc. via serial communication

Store Settings
COMM. Parameters

Enabled/
Disabled

Same

as

Store Settings Main Settings

on

page 28.
Note:
After changing communication parameters and storing
them, control power must be switched OFF and ON to
load new communication parameters.

42