GE Industrial Solutions ASTAT XT User Manual

Page 15

Advertising
background image

15

• Technical Specifications

Terminal Function

Description

Terminal 15

Programmable Fault Output
relay (Common)

When the At Fault Close function is selected, the relay
is energized upon fault. The contact returns to its original
position when one of the following occurs:

The fault has been removed and ASTAT-XT was reset.

Disconnection of Control Supply

When the At Fault Open function is selected, the relay is
energized immediately when the Control Supply is connected
and de-energizes when one of the following occurs:

Fault

Control Supply disconnection

Refer to section

4.7.8 page 40 for PROG. Fault Relay

programming.

Terminal 16

Programmable EOR (End Of
Ramp) Output relay (N.O.)

Voltage free 8A, 250VAC, 2000VA max. changes its position at
the end of ramp, after an adjustable time delay (Contact
Delay), 0 – 120 sec.

Terminal 17

Programmable EOR (End Of
Ramp) Output relay (N.C.)

The contact returns to its original position when Energy
Save

is operated, on Soft Stop or Stop signals, on Fault

condition, or upon voltage outage.

Terminal 18

Programmable EOR (End Of
Ramp) Output relay (Common)

The EOR (End Of Ramp) contact can be used for:

Closing a bypass contactor

Activating a valve after compressor has reached full speed

Loading a conveyor after motor reached full speed.

Refer to section

4.7.3 page 29 for EOR Relay Delay

programming

Terminal 19

External Fault input

Input from a N.O. contact that is connected between
terminals 19 and 21. The ASTAT-XT will trip 2 seconds after
the contact closes.
Notes:

Wires connecting the External Fault contact to terminal 19

should not exceed 1 meter in length.

External Fault can be used only when terminal 21 is

connected to neutral or ground.

Only potential free contacts may be connected to terminal

19.

Do not connect any voltage to terminal 19.

Any connection of voltage to this terminal may disrupt

ASTAT-XT operation, and cause ASTAT-XT or motor damage.

Refer to section

8.12 page 67 for the External Fault wiring

diagram.

Terminal 21

Neutral connection

When a mains neutral wire is available, connect terminal 21
to neutral. Terminal 21 serves only as a voltage reference to
the control circuitry.
Caution:

ASTAT-XT circuitry incorporates an internal artificial neutral,

which should only be used, when the mains system is not
grounded and mains neutral connection is not available.

Only potential free contacts may be connected to terminal

21.

Do not connect any voltage to terminal 21.

Any connection of voltage to this terminal may disrupt
ASTAT-XT operation, and cause ASTAT-XT or motor damage.

Refer to section

8.1 on page 62 for terminal 21 connection.