Standard starting procedure – GE Industrial Solutions ASTAT XT User Manual

Page 54

Advertising
background image

54

• Starting Procedure


6.1

Standard Starting Procedure





















































See next page

Connect Control Supply voltage. On LED will light.
Review all parameters with the Mode and Select keys. Set parameters as required.
If necessary, return to Default Parameters (refer to section

4.5.3 page 63).

Connect mains voltage to the line terminals of the ASTAT-XT.
Set LCD to show Motor Current.

Apply START command

Motor starts to turn

shortly after START

signal?

Initial inrush current

or mechanical shock

is too high?

Increase Starting Voltage and

start again

Decrease Starting Voltage and
start again

Speed accelerates

smoothly to

nominal?

Apply the STOP command and wait until the motor

stops.

Current during

acceleration is too

high?

Motor speed does

not accelerate to

nominal?

Yes

No

Yes

No

No

Yes

Yes

No

No

Yes

A

Increase Current Limit

Decrease Current Limit

Slightly increase Starting Voltage
and CURRENT LIMIT settings to allow for load

changes.