Appendix C - DeviceNet™ to Modbus™ Gateway

3

Run1 (Forward)

BOOL

0

Get / Set Bit 2: 40752

Bit 8-15: 0x5A

4

Run2 (Reverse)

BOOL

0

Get / Set Always 0

7 Running1

(Forward)

BOOL

0

Get

Bit 11: 40257

9

Ready

BOOL

0

Get

Bit 5: 40257

10

Faulted

BOOL

0

Get

Bit 15: 40257

11

Warning

BOOL

0

Get

Bit 6: 40257

15

Ctrl From Net

BOOL

1

Get

Always 1

100

Control Word

UINT

0

Get / Set 40752

(Read always 0-
since register is
not readable)

C.8.3.

Common Services

Implemented for

Service
Code

Class Level

Instance Level

Service Name

05

HEX

No

Yes

Reset

0E

HEX

Yes

Yes

Get Attribute Single

10

HEX

No

Yes

Set

Attribute

Single

C.9. Modbus / Serial Object (65

HEX –

1 Instance)

C.9.1.

Class Attributes (Instance 0)

Attribute
ID

Name DeviceNet

Data Type

Data Value

Access
Rule

1 Revision

UINT

1 Get

C.9.2.

Instance Attributes (Instance 1)

Attribute
ID

Name DeviceNet

Data Type

Data Value

Access
Rule

1

Modbus Slave ID (1-247)

USINT

1

Get /
Set

53

2 Baud

Rate

0 = 4800
1 = 9600
2 = 19200

USINT 2

Get

/

Set

53

3 Parity

0 = 8N
1 = 8E
2 = 8O

USINT 1

Get

/

Set

53

10

Timeout (milliseconds) (10ms
– 60000ms)

UINT 500 Get

/

Set

53

100

Number of Valid Reads
(since power up)

UDINT 0

Get

101

Number of Read Errors
(since power up)

UDINT 0

Get

102

Number of Read Timeouts
(since power up)

UDINT 0

Get

110

Number of Valid Write
(since power up)

UDINT 0

Get

111

Number of Write Errors
(since power up)

UDINT 0

Get

112

Number of Write Timeouts
(since power up)

UDINT 0

Get

53

Stored to NVRAM