12 external fault, 13 line contactor – GE Industrial Solutions ASTAT XT User Manual

Page 67

Advertising
background image

67

• Application diagrams

8.12

External Fault

Note:
Switch E can be used as an External
Fault

input only when terminal 21 is

connected to neutral or ground.

8.13

Line Contactor

Notes:

Typical wiring when ASTAT-XT is retrofitted into an existing system to reduce modifications in existing

installations.

Start signal is switched ON upon closure of the line contactor. The ASTAT-XT will operate as long as

the line contactor is energized.

Control Supply obtained from mains must match the ASTAT-XT Control Supply voltage.

It is recommended that terminals 1-3 are always connected to Control Supply voltage.

Soft stop can not be applied for this wiring diagram. If soft stop is required, the line contactor can be

held by the Immediate Relay (RUN relay) contacts because the relay is de-energized only at the end
of the soft stop.

Verify that N.O. contact C1 closes after the main contactor closes. ASTAT-XT requires 500 mSec. delay

for the start signal after the line contactor is closed. If it closes prior to that, Undervoltage FLT
will occur. It is recommended to use a time delay timer to prevent possible faults.