Appendix C - DeviceNet™ to Modbus™ Gateway

ID Data

Type

Rule

1 Revision

UINT

1 Get

C.14.2.

Instance Attributes (Instance 1)

Attribute
ID

Name Range

Default
Value

Access
Rule

Modbus
Address

1 Starting

VOLT-2

10-80

30

Get/Set

40049

2 Current

Limit-2

100-
500

400 Get/Set

40050

3 Ramp

UP-2 1-90

10

Get/Set

40051

4 Ramp

DOWN-2

1-30

10

Get/Set

40052

5 Motor

Current-2

5-1400

105

Get/Set

40053

C.14.3.

Common Services

Implemented for

Service
Code

Class Level

Instance Level

Service Name

0E

HEX

Yes

Yes

Get Attribute Single

10

HEX

No

Yes

Set

Attribute

Single

C.15. Slow SP & Saving Parameters Object (75

HEX –

1 Instance)

C.15.1.

Class Attributes (Instance 0)

Attribute
ID

Name DeviceNet

Data Type

Data Value

Access
Rule

1 Revision

UINT

1 Get

C.15.2.

Instance Attributes (Instance 1)

Attribute
ID

Name Range

Default
Value

Access
Rule

Modbus
Address

1 Energy

Saving 0-10

10

Get/Set

40057

2

Slow Speed TRQ.

1-10

8

Get/Set

40058

3 Max_Slow_SP_Time

1-250

30

Get/Set

40059

C.15.3.

Common Services

Implemented for

Service
Code

Class Level

Instance Level

Service Name

0E

HEX

Yes

Yes

Get Attribute Single

10

HEX

No

Yes

Set

Attribute

Single

C.16. Fault Settings Object (76

HEX –

1 Instance)

C.16.1.

Class Attributes (Instance 0)

Attribute
ID

Name DeviceNet

Data Type

Data Value

Access
Rule

1 Revision

UINT

1 Get

C.16.2.

Instance Attributes (Instance 1)

Attribute
ID

Name Range

Default
Value

Access
Rule

Modbus
Address

1 Phase

Loss 0-1

0

Get/Set

40064

2 Phase

Sequence

0-1

0

Get/Set

40065

5 Auto_Reset

0-1

1

Get/Set

40066

6 Thermistor_Type

0-1

0

Get/Set

40067

7 Thermistor_Trip

0-100
(Tenth Kohm)

0 Get/Set

40068

8

Undercurrent RST

10-120 &
121 - OFF

121 Get/Set

40069