• Control Keypad

Soft Start Curves 1-3

- Pump Control - Induction motors produce peak torque of up to 3 times the rated

torque towards the end of starting process. In some pump applications, this peak may cause a pressure surge in the
pipes.
Soft Start Curves 1, 2, 3

– During acceleration before reaching peak torque, the Pump Control Program

automatically controls the voltage ramp-up, thus, reducing peak torque.

Choice of four pump control acceleration curves: 0!, 1!, 2!, 3!



Soft Start Curve 4 (Torque)

– Torque Controlled acceleration - This provides a smooth time-controlled

torque ramp for the motor and the pump.

Note:
Always start with Soft Start Curve 0. If towards the end of ramp, peak torque is too high (pressure is too high)
proceed to Soft Start Curve 1, 2, 3 or 4 in that order.