39

• Control Keypad

Function &

Default

Range

Unit

Description

Thermistor Type
PTC

PTC/NTC

Sets input Thermistor Type
Measures the motor’s thermistor resistance and trips the
ASTAT-XT when the level decreases below set level.

Thermistor Trip
Disabled

Disabled,
0.1–10Kohm

Sets ASTAT-XT’s Thermistor Trip mode of operation.
Note:
Thermistor Trip has a factory preset time delay of 2 sec.

Undercurrent RST
Disabled

10–120min.,
Disabled.

Sets ASTAT-XT’s Undercurrent Reset time delay.
If the Undercurrent RST setting is OFF then ASTAT-XT will
not automatically reset after an Undercurrent Trip fault
occurs.
If you set the Undercurrent RST setting to a time value
then ASTAT-XT will automatically reset with a delay (the time
defined for Undercurrent RST). If the start command is not
removed, the motor will restart automatically after the delay
time.
During the delay time a message U/C Fault Retry In:
XX Min.

is displayed.

Refer to section

4.7.2 on page 27 for details on setting of

Undercurrent Trip

.

Store Settings
Fault Settings

Same

as

Store Settings Main Settings

on page 28.