Figure 122: battery equalizing, Figure 123: time left, Figure 124: last test – MaxPower Corp Gamatronic Power+ M50-RM User Manual

Page 105: Figure 125: battery current

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

89

2.

View next automatic equalizing, remaining equalizing time, total rectifier current, and
battery (charging) current:

[Main Menu > BATTERY >

▼]

Next automatic equalizing: 02 days
Remaining equalizing time: ___ minutes
Rectifiers total current : 0050A
Battery current : 053.0A

Figure 122: Battery equalizing

3.

View the maximum estimated time left, battery test in progress time, battery voltage,
battery (charging) current, last test result, and days left:

[Main Menu > BATTERY >

▼ > ▼]

Max/estim time left : 00:00:00 /--:--:--
Battery test in progress for: 00:00:00
Batt. volt: 400.0V Batt.current: 010
Last test: PASSED Days left: 027

Figure 123: Time left

4.

View battery status and status of the last test:

[Main Menu > BATTERY >

▼ > ▼ > ▼]

1> Battery#1: PASSED Last test: PASSED

Figure 124: Last test

5.

View battery (charging) current:

[Main Menu > BATTERY >

▼ > ▼ > ▼ > ▼]

Batt1 curr: 052.1A Batt curr: 052.1A

Figure 125: Battery current