175

UPS capacity

10 kVA

20 kVA

30 kVA

40 kVA

50 kVA

Dimensions (U.S. measurements) incl. exterior cabinet, excl. batteries
Height

78.4 in. (including cabinet legs)

Width

24 in

Depth

39.1 in

Weight

(lbs)

766 788 811 833 856

Dimensions (metric measurements) incl. exterior cabinet, excl. batteries
Height

1990 mm (including cabinet legs

Width

611 mm

Depth 994

mm

Weight

(kg)

347.4 357.6 367.8 378.0 388.2

Acoustic Noise
Noise (dBA) with half load

48

52

53

54

55

Noise (dBA) with full load

51

54

55

57

58

SYSTEM CONTROLLER – TECHNICAL DATA

Microcontroller core

16 bit

Display

4 × 40 characters LCD with backlight

Other indicators

8 LEDs, buzzer

Analog input channels

3 for battery current measurement
1 for temperature measurement

Voltage-free user input channels
(dry contacts)

8

Real Time Clock (RTC)

Yes (operates for 2 weeks without power)

Power meter

kVA, kW, PF

Volt-free outputs (dry contacts)

6 outputs, rated 50V/1A

RS232 user port

Yes, isolated

Optional communication

TCP/IP, GPRS/SMS wireless communications (optional)

Communications with system modules

Serial, isolated

Events log

255 events

System operation without controller

Unchanged

On-screen parameters

Load bar-graph
3-phase voltages
3-phase currents
Battery voltage
Status of each UPS module
Static-switch parameters and status
Battery sensor temperature

Alarms
(floating output relay contacts,
each rated for max. 48 Vdc 1 A)

Ac failure
Dc failure
UPS module(s) failure
Load on bypass
Battery test failure
Over/under temperature
Overload

Power requirements

3 × 208 Vac / ±216 Vdc 15 W