3 setting battery over/under temperature alarms, Setting battery over/under temperature alarms, Figure 146: set bat-hi – MaxPower Corp Gamatronic Power+ M50-RM User Manual

Page 113: Figure 147: alarm set menu, Figure 148: over/under temperature menu, Figure 149: set battery maximum temperature alarm

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

97

7.

Use the arrow keys to set BAT-HI, press Ent, and then Esc:

[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT > BAT-HI]

FLOATING CHARGE ALARM SETUP

VOLTAGE SETTING: 340.0V

Figure 146: Set BAT-HI

8.8.3

Setting Battery Over/Under Temperature Alarms

1. Select

TEMPERATURE:

[Main Menu > SETUP > (password) > ALARM SET]

1> AC VOLT 5> --------- 9>INTEGRAT.
2> FLOAT VOLT 6> ---------
3> --------- 7> TEMPERATURE
4> --------- 8> ---------

Figure 147: Alarm set menu

2. Select

OVER TEMPERATURE:

[Main Menu > SETUP > (password) > ALARM SET > Temperature]

1> OVER TEMPERATURE
2> UNDER TEMPERATURE

PLEASE SELECT

Figure 148: Over/Under temperature menu

3.

Use the arrow keys to set the battery maximum temperature alarm value and press Ent:

[Main Menu > SETUP > (password) > ALARM SET > Temperature > OVER TEMPERATURE]

SET OVER TEMPERATURE ALARM VALUE
( 2 – 99) DEGREES

45

Figure 149: Set battery maximum temperature alarm

Advertising