8 special terminal connections, Special terminal connections, Figure 34: special purpose terminals in stsw tray – MaxPower Corp Gamatronic Power+ M50-RM User Manual

Page 60: Figure 35: close-up of special purpose terminals

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

44

5.8

Special Terminal Connections

This section describes the special-purpose terminal connections of the POWER+ RM 50 kVA.

Special-purpose connections are located inside the static switch tray. To access the special-
purpose terminals, the static switch tray must be partially slid out (after disconnection of the UPS
from all voltage sources and following standard safety procedures). Figure 34 shows a view from
above of the open static switch tray and the location of the special terminal connections. Figure
35 provides a closer look at the connections.

Note: There are also some special purpose connections on the rear of the controller module.

Figure 34: Special purpose terminals in STSW tray

STSW communication bus

Load on

bypass

(N.O.)

1

2

E.P.O.

(N.O.)

1

2

Batt. CB

trip coil

(N.O.)

1

2

External N.O.

EPO switch

Trip coil

Power

contacts

Contacts close

during bypass

operation

Battery

C.B.

To controller

CB aux. contacts

provide

"on/off" indication

Figure 35: Close-up of special purpose terminals

Advertising