Bypass Operation (Manual)

If the Power+ is manually switched to bypass operation by pressing the Inv/Byp button, the load
is transferred to the mains ac input line. Transfer back to normal operation must be performed
manually. The red alarm indicator flashes (Figure 23).

4.9.5

Emergency Power off – EPO (Manual)

The EPO button is for use by the user, in emergencies only. The EPO button cuts the supply to
the load with immediate effect and cannot be reset. Once switched OFF by the EPO, the

POWER+ must be restarted manually.

The EPO switch must be an N.O.-type, rated for at least 24 Vdc, 1 A.