MaxPower Corp Gamatronic Power+ M50-RM User Manual

Page 134

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

118

2. Select

ENABLE SHUTDOWN by long AC FAIL (Off) and press Ent to toggle

enable/disable:

[Main Menu > SETUP > (password) > Battery > Enable/Dis Options]

1> ENABLE SHUTDOWN by long AC FAIL (Off)
2> ENABLE Current Sensors (Off)
3> ENABLE BATT Temperature sensor (Off)
Select & Press To toggle Enable/Disable

1> DISABLE SHUTDOWN by long AC FAIL(On )
2> ENABLE Current Sensors (Off)
3> ENABLE BATT Temperature sensor (Off)
Select & Press To toggle Enable/Disable

Figure 215: Enable/Disable shutdown by long AC failure

Note: Option 1 in Figure 215 allows the user to enforce shutdown after a given length of input ac

failure, even when the batteries are still fully charged.

Item 2, ENABLE Current Sensors (Off) and item 3, ENABLE BATT Temperature
sensor (Off)
in the screens shown in Figure 215 toggle between enable/disable in the
same manner as item 1, ENABLE SHUTDOWN by long AC FAIL (Off).