10 installation procedure, Installation procedure, Table 10: installation steps – MaxPower Corp Gamatronic Power+ M50-RM User Manual

Page 63

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

47

5.10

Installation Procedure

Table 10: Installation steps

OPERATION

1.

Remove rear covers and connect ac input and output power cables to terminals according to markings as shown
in this User Guide and according to connection schematic.
Verify correct phase sequence between board and UPS
See section

5.1 for recommended wire size and tightening torque.

2.

Connect ground lines to busses according to markings as shown in the connection diagram
(Figure 24 on page 31).
Verify secure connections. See section

5.1 for recommended wire size and tightening torque.

3.

Connect the dc power cables of the battery cabinets to the UPS terminals according to markings as
shown in the connection diagram (see step 2 above). Connect neutral and ground lines to busses as
per the connection diagram.

Note: If the UPS is delivered without batteries, Gamatronic is not responsible for any damage or
malfunction due to incorrect wiring of the batteries.

Verify correct polarity of the connections (+ / N / -) Between the Battery Cabinets C.B.s / Terminals and
the UPS terminals. Auxiliary contacts of Battery C.B.s are connected to UPS Controller inputs “Bat CB”
and “Com” as marked.

4.

If an external battery cabinet is being used, before turning on the battery cabinet circuit breaker perform the
following two checks:

4.1) Measure the voltage between the (+) and (–) terminals on the battery cabinet. The voltage must

be within the range of 384–432 Vdc. If the voltage is not within this range, determine what the
problem is and resolve it before continuing with system start-up.


4.2) On the battery cabinet, measure the voltage between the (+) terminal and the Neutral terminal, and

between the (–) terminal and the Neutral terminal. Both measurements should be within the range
of 196–216 Vdc. If a reading outside of that range is obtained, determine what the problem is and
resolve it before continuing with system startup.

5.

An external N.O. EPO switch may be connected according to connection schematic.
EPO wiring and switch rating must be rated for at least 1A / 24 Vdc.

6.

Before connecting power to each system verify again that all connections are secure and are according to
instructions and schematics.

7.

Follow the instructions in section

5.11, which begins on page 48.