3 set date and time and serial number, 4 define the ip address of the power, Set date and time and serial number – MaxPower Corp Gamatronic Power+ M50-RM User Manual

Page 75: Define the ip address of the power, Figure 64: date and time, Figure 65: site number, Figure 66: network menu

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

59

5.14.3

Set Date and Time and Serial Number

To verify the date and time set in the System Controller and make sure that they are correct:

1. Use

the and

keys to select the year, month, day, hour, minute, or second you wish

to modify, then use the

and

keys to set the correct value for the selected item.

Press Ent:

[Main Menu > SETUP > (password) > Time]

Set real time

Year Month Day Hour Min Sec
2011 09 30 23 58 00

Figure 64: Date and time

2.

Enter the serial number of the Power+ system in the System Controller, and then press
Ent:

[Main Menu > SETUP > (password) > Site]

Site number: 013271

Figure 65: Site number

Note: The serial number of Power+ is on a bar-code label at the bottom of the unit, on the left

hand side.

5.14.4

Define the IP Address of the Power+

This procedure assigns the Power+ an address within the domain of the customer's computer
network.

1.

Obtain IP, gateway, and mask addresses from the system administrator of the
organization for the Power+ system.

2. Select

Set IP ADDRESS in the Network menu:

[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network]

1> Set IP ADDRESS 157.211.000.253
2> Set GATEWAY 157.211.000.251
3> Set MASK 255.255.255.000
4> Store 5> SNMP factor Select:1

Figure 66: Network menu