Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

131

5. Press

Ent to continue:

[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration > DC-I
Calibration]

1> Calibrate Battery #1 Current

Figure 254: Calibrating DC current

6.

Using the arrow keys, set the actual current and then press Ent:

[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration > DC-I Calibration
> Ent]

CURRENT METER #01 CALIBRATION
Enter the value of the actual current:

02000 (X0.1)A

Figure 255: Entering actual current

8.12.3.7

Selecting Standalone or Parallel Operation

1. Select

Parallel/StandAlone:

[Main Menu > SETUP > (password) > Ent > Service > Configure]

1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND

Figure 256: Service > Configure menu

2. Select

Stand Alone or Parallel by using the

▲▼arrow keys and Ent:

[Main Menu > SETUP > (password) > Ent > Service > Configure > Parallel/StandAlone]

--- Parallel / Stand-Alone Setup ---
SELECT - 1: Stand Alone (selected)
SELECT - 2: Parallel

Figure 257: Setting standalone or parallel operation