Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

12

2.2

External battery cabinet (option)

An external battery cabinet is available as an option (cat. no. 29B020128-PPE).
This external battery cabinet can be used instead of the built-in battery box where longer
duration backup is required. The built-in battery box and the external cabinet cannot be used
together.

The external battery cabinet contains two battery boxes identical to the built-in battery box.
Each battery box contains eight drawers of batteries. Each drawer contains eight batteries.

The external battery cabinet should be located as close to the UPS as is practical.

2.2.1

Dc wiring

When the optional external battery cabinet is used (cat. no. 29B020128-PPE) instead of the built-
in battery box, connect the battery cabinet to the UPS's battery terminals (item 3 in Figure 2)
using 4 copper wires of size 1 AWG, rated 75 °C.