1 setting the floating charge, Setting the floating charge, Figure 218: setup menu – MaxPower Corp Gamatronic Power+ M50-RM User Manual

Page 136: Figure 219: charge setup menu, Figure 220: set floating charge

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

120

8.11.1

Setting the Floating Charge

1. Select

Charge:

[Main Menu > SETUP > (password) > Ent]

1> Alarm set 5> Time 9> Silicon
2> Module conf. 6> Site
3> Battery 7> Password #1
4> Charge 8> Service

Figure 218: Setup menu

2. Select

Floating parameters setup.:

[Main Menu > SETUP > (password) > Charge]

1> -----
2> Floating parameters setup.
3> ----- (Eq:off)
4> ----- 1

Figure 219: Charge setup menu

3.

Using the arrow keys, set the floating charge, press Ent, and then press Esc:

[Main Menu > SETUP > (password) > Charge > Floating parameters setup.]

Floating charge setup

Voltage setting: 432.0V

Figure 220: Set floating charge