1 setting ac voltage alarms, Setting ac voltage alarms, Figure 134: setup menu – MaxPower Corp Gamatronic Power+ M50-RM User Manual

Page 110: Figure 135: alarm setup menu, Figure 136: ac alarms menu, Figure 137: set ac alarm voltage levels

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

94

2.

Select Alarm set:

[Main Menu > SETUP > (password) > Ent]

1> Alarm Set 5> Time 9> Silicon
2> Module Conf. 6> Site
3> Battery 7> Password #1
4> Charge 8> Service 1

Figure 134: Setup menu

8.8.1

Setting Ac Voltage Alarms

1. Select

AC VOLT:

[Main Menu > SETUP > (password) > ALARM SET]

1> AC VOLT 5> --------- 9>INTEGRAT.
2> FLOAT VOLT 6> ---------
3> --------- 7> TEMPERATURE
4> --------- 8> ---------

Figure 135: Alarm setup menu

2. Select

Set AC High & Low Alarm Levels:

[Main Menu > SETUP > Ent > (password) > Ent > ALARM SET > AC VOLT]

1> SET AC HIGH & LOW ALARM LEVELS
2> SET AC ALARMS HYSTERESIS

PLEASE SELECT 1

Figure 136: Ac alarms menu

3.

Use the arrow keys to update values and press Ent:

[Main Menu > SETUP > Ent > (password) > Ent > ALARM SET > AC VOLT > Set AC High &
Low Alarm Levels]

AC VOLT SETUP: NOMINAL 110/120 VAC
---- AC ALARM SETUP ----
AC-LOW AC-HIGH
090V 138V

Figure 137: Set ac alarm voltage levels