5.11.1

Changing the Power+ output voltage

1.

Press the Enter key to display the main menu, and then select SETUP:

1> SYSTEM 4> HISTORY 7> SETUP
2> UPS MODULE 5> BATTERY 8> STATIC SW
3> SELFTEST 6> ALARM 9> _____
NAVIGATE: <UP, DOWN> 1 SELECT: <ENTER>

Figure 44: Main menu

2.

Enter the password. (The default password is pressing the "left-arrow" key eight times,
and then the Enter key:

[Main Menu > SETUP]

POWER+ System Setup
Type in Level-1 PASSWORD, THEN – ENTER
Your privilege will expire after 15 min.
PASSWORD:________

Figure 45: Level 1 password access

3. Select

Module/s voltage:

[Main Menu > SETUP > (password) > Module conf.]

1. Num of phase 5.Output Adjust
2. Module/s frequency 6.Frequency Limits
3. Module/s voltage 7.DC Calibration
4. Update Vo/Fr/ph 8.AC Calibration

Figure 46: Module Config. setup menu

4. Use

the

▲▼arrow keys to set the module/s voltage, press Ent, and then Esc:

[Main Menu > SETUP > (password) > Module conf. > Module/s voltage]

Module/s voltage 4: 118V
1: 110V 5: 120V
2: 113V 6: 125V
3: 115V (selected) 5: 130V

Figure 47: Setting the Module/s voltage