7 defining email notification targets, Defining email notification targets, Figure 318: defining email notification targets – MaxPower Corp Gamatronic Power+ M50-RM User Manual

Page 178: Table 21: fields in the email notifications screen

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

162

9.3.7.7

Defining email notification targets

The Web interface enables you to have notifications of system alarm conditions sent by email. To
use this feature, the outgoing email server must be defined in the “E-mail notifications screen”,
accessible from the Configuration menu.

Figure 318: Defining email notification targets

Table 21: Fields in the email notifications screen

F

IELD

D

ESCRIPTION

SMTP server
address

DNS name or IP address of the outgoing email server. The Power+ must
be defined to the email server as NOT requiring a login.

SMTP port

Predefined SMTP port for the notification messages

Send as:

The “from” address in the outgoing email. Note: some email servers have
an anti-spam feature that requires the “from” address to be a valid, existing
address.

Recipients

In each line under the “Recipients” header a single email address can be
entered in standard format. For example:
[email protected]” (without the quotes).
A single email address representing a list of addresses can also be
entered.