POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

104

8.9.6

Setting Frequency Limits

1. Select

Frequency Limits:

[Main Menu > SETUP > (password) > Module conf.]

1. Num of phase 5.Output Adjust
2. Module/s frequency 6.Frequency Limits
3. Module/s voltage 7.DC Calibration
4. Update Vo/Fr/ph 8.AC Calibration

Figure 168: Module Config. setup menu

2. Using

the

▲▼ keys set the frequency limits, press Ent, and then Esc:

[Main Menu > SETUP > (password) > Module conf. > Frequency Limits]

--- Set frequency limits ---
1: No Change 4: +/- 3Hz
2: +/- 1Hz (slctd) 5: +/- 4Hz
3: +/- 2Hz 6: +/- 0.5Hz

Figure 169: Select the frequency limits

8.9.7

Calibrating DC Voltage

1. Select

DC Calibration:

[Main Menu > SETUP > (password) > Module conf.]

1. Num of phase 5.Output Adjust
2. Module/s frequency 6.Frequency Limits
3. Module/s voltage 7.DC Calibration
4. Update Vo/Fr/ph 8.AC Calibration

Figure 170: Module Config. setup menu

2. Select

either

Calibrate Positive Voltage or Calibrate Negative Voltage and then

press Ent:

[Main Menu > SETUP > (password) > Module conf. > DC Calibration]

--- MODULES DC VOLTAGE CALIBRATION ---
SELECT – 1: Calibrate Positive Voltage
SELECT – 2: Calibrate Negative Voltage
Then press ENTER to continue

Figure 171: Calibrate Positive or Negative Voltage