3 setting module/s voltage, 4 update voltage/frequency/phase, Setting module/s voltage – MaxPower Corp Gamatronic Power+ M50-RM User Manual

Page 118: Update voltage/frequency/phase, Figure 160: module config. setup menu, Figure 161: setting the module/s voltage, Figure 162: module config. setup menu, See section

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

102

8.9.3

Setting Module/s Voltage

1. Select

Module/s voltage:

[Main Menu > SETUP > (password) > Module conf.]

1. Num of phase 5.Output Adjust
2. Module/s frequency 6.Frequency Limits
3. Module/s voltage 7.DC Calibration
4. Update Vo/Fr/ph 8.AC Calibration

Figure 160: Module Config. setup menu

2. Use

the

▲▼arrow keys to set the module/s voltage, press Ent, and then Esc:

[Main Menu > SETUP > (password) > Module conf. > Module/s voltage]

Module/s voltage 4: 118V
1: 110V 5: 120V
2: 113V 6: 125V
3: 115V (selected) 5: 130V

Figure 161: Setting the Module/s voltage

8.9.4

Update Voltage/Frequency/Phase

1. Select Update Vo/Fr/ph:

[Main Menu > SETUP > (password) > Module conf.]

1. Num of phase 5.Output Adjust
2. Module/s frequency 6.Frequency Limits
3. Module/s voltage 7.DC Calibration
4. Update Vo/Fr/ph 8.AC Calibration

Figure 162: Module Config. setup menu

2. Press

Ent to update, and then Esc:

[Main Menu > SETUP > (password) > Module conf. > Update Vo/Fr/ph]

Nominal Voltage & Frequency

have been sent to all modules.

Please verify all modules were updated!

Exit this mode by pressing Esc.

Figure 163: Updating the Module/s voltage/frequency/phase