POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

130

8.12.3.6

Calibrating DC Currents

1. Select

Calibration:

[Main Menu > SETUP > (password) > Ent > Service > Configure]

1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND

Figure 250: Service > Configure menu

2. Select

DC-I Offset removal:

[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration]

1> ----- 5> -----
2> DC-I Offset removal 6> -----
3> DC-I Calibration 7> -----
4> ----- Select

Figure 251: DC-I menu

3.

Follow screen instructions:

[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration > DC-I Offset
removal]

To remove current offsets,
DISCONNECT BATTERIES and LOAD first,
Then, press ENTER.
Else, press Esc. (0516 0517 0517)

Figure 252: Remove current offsets

4. Select

DC-I Calibration:

[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration]

1> ----- 5> -----
2> DC-I Offset removal 6> -----
3> DC-I Calibration 7> -----
4> ----- Select

Figure 253: DC-I menu