2 total number of upss, 3 total number of batteries, Total number of upss – MaxPower Corp Gamatronic Power+ M50-RM User Manual

Page 143: Total number of batteries, Figure 238: service > configure menu, Figure 239: set total number of upss, Figure 240: service > configure menu, Figure 241: set total number of batteries

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

127

8.12.3.2

Total Number of UPSs

1. Select

# OF UPSs (total):

[Main Menu > SETUP > (password) > Ent > Service > Configure]

1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND

Figure 238: Service > Configure menu

2.

Use the arrow keys to set the total number of UPSs and then press Ent:

[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF UPSs (total)]

Set number of UPSs (total)

04 (02 redundant)

Figure 239: Set total number of UPSs

8.12.3.3

Total Number of Batteries

1. Select

# OF BATT:

[Main Menu > SETUP > (password) > Ent > Service > Configure]

1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND

Figure 240: Service > Configure menu

2.

Use the arrow keys to set the total number of batteries and then press Ent:

[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF BATT]

Set Number Of Batteries (0 to 3)

02

Figure 241: Set total number of batteries