113

2. Select

Set absolute minimum output voltage:

[Main Menu > SETUP > (password) > Battery > Temp. Compensat. > Set ABSOLUTE Max &
Min Voltages]

1> Set absolute minimum output voltage
2> Set absolute maximum output voltage
--== Active in floating mode only ==--
Please select. 1

Figure 196: Select Set absolute minimum output voltage

3.

Using the arrow keys, set the absolute minimum voltage when compensating and then
press Ent:

[Main Menu > SETUP > (password) > Battery > Temp. Compensat. > Set ABSOLUTE Max &
Min Voltages > Absolute MINimum Voltage While Cmpensat.]

Absolute minimum voltage while cmpensat.

Voltage setting: 400.0V

Figure 197: Set absolute minimum output voltage when compensating

4. Select

Set absolute maximum output voltage:

[Main Menu > SETUP > (password) > Battery > Temp. Compensat. > Set ABSOLUTE Max &
Min Voltages]

1> Set absolute minimum output voltage
2> Set absolute maximum output voltage
--== Active in floating mode only ==--
Please select. 1

Figure 198: Select Set absolute maximum output voltage

5.

Using the arrow keys, set the absolute maximum voltage when compensating, press
Ent, and then Esc:

[Main Menu > SETUP > (password) > Battery > Temp. Compensat. > Set ABSOLUTE Max &
Min Voltages > Absolute MAXimum Voltage While Cmpensat.]

Absolute maximum voltage while cmpensat.

Voltage setting: 460.0V

Figure 199: Set absolute maximum output voltage when compensating