Additional battery information

Free air circulation around the batteries is extremely important for proper battery safety. If
the Power+ is installed in a cabinet, the cabinet must have sufficient ventilation openings
to permit free air circulation around the batteries.

This means that solid glass or acrylic-type door panels are not suitable for a cabinet
housing the Power+, neither for the front cabinet door nor for the rear door.

Protect the batteries from moisture, dampness, and foreign substances.

The temperature of the battery's surroundings influences the batteries' useful lifetime.

Table 2: Battery lifetime vs environmental temp. (illustrative)

E

NVIRONMENTAL

TEMPERATURE

A

CHIEVABLE PERCENTAGE OF

BATTERY

'

S RATED LIFETIME

68 °F (20 °C)

100 %

86 °F (30 °C)

50 %

104 °F (40 °C)

20 %

If the UPS is delivered without batteries, Gamatronic is not responsible for any damage or
malfunction due to incorrect wiring of the batteries.

Please refer to the battery manufacturer’s data sheets for additional information.

When replacing internal batteries, replace with the same number and type!

B

ATTERY

M

ANUFACTURER

P

ART

N

UMBER

HR 1290W

B

ATTERY DESCRIPTION

CSB Battery Co.,
a.k.a CSB Battery Technologies
a.k.a CSB Battery Europe

12 V, 90 W, 22.5 Ah,
valve-regulated lead-acid