Figure 57: service menu, Figure 58: configure menu, Figure 59: # of upss (total) – MaxPower Corp Gamatronic Power+ M50-RM User Manual

Page 73: Figure 60: # of upss (redundancy)

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

57

5. Select

Configure, option 5, to configure the Power+ modules:

[Main Menu > SETUP > (password) > Ent > Service]

1> ------ 4> DryOut Test 7> --------
2> UPSs 5> Configure 8> Powr.Calib
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter

Figure 57: Service menu

6. Select

# UPSs (total), option 2, to specify the total number of modules in the system:

[Main Menu > SETUP > (password) > Ent > Service > Configure]

1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND

Figure 58: Configure menu

7.

Use the arrow keys to specify the total number of modules installed in the Power+, and
then press Ent:

[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF UPSs (total)]

Set number of UPSs (total)

04 (02 redundant)

Figure 59: # of UPSs (Total)

8. Select

1,

# of UPSs (Redundancy) in Figure 58 to specify the number of modules used

for redundancy:

[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF UPSs (redundancy)]

Set number of UPSs (Redundancy)

01 (04 total)

Figure 60: # of UPSs (Redundancy)

Note: The redundant modules are designated to replace other system modules when they stop

working. For example, a 100-kVA system with 10 modules of which two are configured for
redundancy can deliver a maximum of 80 kVA.