2 power+ shutdown (switching to bypass), 3 power+ total shutdown (no ac output), Power+ shutdown (switching to bypass) – MaxPower Corp Gamatronic Power+ M50-RM User Manual

Page 84: Power+ total shutdown (no ac output), Figure 81: main screen – switching to bypass, Figure 82: bypass indication, Figure 83: main screen – total shutdown

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ RM

50

K

VA, N.Am. Std. – User Guide, Release 1.9

68

6.2

POWER+ Shutdown (Switching to Bypass)

1.

Switch the load OFF.

2.

Press twice on the On/Off button.

3.

Wait 2 minutes for the POWER+ to shut down. The control screen will indicate UPS OK
(OFF).

LOAD LEVEL ---22:21:18---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (OFF)
L3:__________ 000A, 120V STSW OK (BYP)

Figure 81: Main screen – switching to bypass

Note: This does NOT switch the entire POWER+ OFF. Power is still delivered to the load but in

bypass.

Figure 82: Bypass indication

6.3

POWER+ Total Shutdown (No Ac Output)

1.

Switch the load OFF.

2.

Press and hold the On/Off button for 10 seconds.

3.

The control screen will indicate UPS OK (OFF).

LOAD LEVEL ---23:14:40---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (OFF)
L3:__________ 000A, 120V STSW Warning !

Figure 83: Main screen – total shutdown

Advertising