Chapter 5 Configuring the PowerSmart+ PQM

Configuring Recorders

PowerSmart+ Power Quality Meter

103

To configure a daily profile log file:

1. Configure your Billing/TOU registers and tariff schedule in the

meter (see

Configuring Billing/Tariff Registers

) first.

2. Double click on the Data Log#16 partition with the left mouse

button.

3. Select the TOU Daily Profile file type.

4. Select the number of season tariffs in your TOU schedule. Add one

additional parameter if you selected to record the Summary (TOU
total) registers as well.

5. Select the maximum number of records you want to be recorded in

the file assuming that a new record will be added once a day.

6. Click OK and send your setup to the meter or save to the meter

database.

Factory Preset Data Log Files

Conventional Data Log #1

Data log #1 is factory preset for 15-min periodic recording of the standard
energy and demand quantities. You can freely change the list of recorded
parameters and the file update rate.

The default list of parameters is shown in the following table.

No.

Parameter

1

kWh import

2

kWh export

3

kW import sliding demand

4

V1 demand

5

V2 demand

6

V3 demand


Periodic recording data is triggered by Setpoint #1 that is linked to the
meter clock. To change the periodic rate at which data is recorded,
change the time interval for the MINUTE INTERVAL trigger in Setpoint #1
(see

Configuring Alarm/Control Setpoints

).

Billing/TOU Profile Data Log #16

Data log #16 is pre-configured for daily billing energy and maximum
demand recording for the last 90 days. It is automatically updated once a
day.

See

Billing Profile Log File

in Appendix E for the file record structure.