Chapter 5 Configuring the PowerSmart+ PQM

Configuring Communications

70

PowerSmart+ Power Quality Meter

Figure 5-2: Communication Setup Dialog Box – Network Setup Tab

The table below lists available network options.

Table 4: Ethernet Setup Options

Parameter

Options

Default

Device IP Address

192.168.0.203

Network Subnet Mask

255.255.255.0

Network Default Gateway

192.168.0.1

TCP Service Port

502 = Modbus/TCP
20000 = DNP3/TCP

502

NOTES

1. The meter provides the permanent MODBUS TCP server on port

502.

2. Selecting the DNP3 TCP service port launches the second DNP3

TCP server allowing simultaneous connections on both TCP
ports. Selecting the MODBUS TCP port disables the DNP3 TCP
server.

The TCP service port can also be changed trough the COM2
serial port setup. Changing the communication protocol for the
port automatically changes the TCP port for the Ethernet.

3. When you change the device network settings through the

Ethernet port, the device port restarts so communication will be
temporarily lost. You may need to wait some additional time
until Power Software restores a connection with your device.