Chapter 5 Configuring the PowerSmart+ PQM

Configuring Communications

74

PowerSmart+ Power Quality Meter

The following table lists available client options.

Table 7: TCP Notification Client Setup Options

Parameter

Options

Default

Description

Client Enabled

NO, YES

NO

Enables operations of the
notification client

Server IP Address

192.168.0.3

The IP address of the notification
server

Server Port

0-65535

502

The TCP service port of the
notification server

Message Exchange
Address

0-65535

1000

The start address of a block
of 16 MODBUS registers for
receiving notification messages

Connections with a remote server are triggered via programmable
setpoints. To send event notifications to a server, configure a setpoint to
respond to desired triggers or to periodic time events and put the
"Notification" action to the setpoint action list (see

Configuring

Alarm/Control Setpoints

).

See the PowerSmart+ PQM Modbus Reference guide for more information
on operation of the notification client and the notification message
structure.