Chapter 5 Configuring the PowerSmart+ PQM

Configuring Communications

68

PowerSmart+ Power Quality Meter

Using Power Software

Select Communications Setup from the Meter Setup menu, and then
click on the Serial Ports Setup tab. In the Port box, select the desired
device port.

Figure 5-1: Communication Setup Dialog Box – Serial Ports Setup Tab

See Table 3

below for available communication options.

Table 3: COM Port Options

Parameter

Options

Default

Description

Protocol

MODBUS ASCII
MODBUS RTU
DNP3
IEC 60870-5
PROFIBUS DP (COM2)

MODBUS
RTU

The communications
protocol for the port
Not changeable on COM2
with the PROFIBUS
module

Interface

COM1: 485 = RS-485
COM2:
232 = RS-232
485 = RS-485
422 = RS-422
Eth = Ethernet
PRO = PROFIBUS DP
GPRS = GPRS modem

RS-485

Communication interface.
Not changeable on COM2
with the Ethernet and
PROFIBUS modules

Device address MODBUS: 1-247

DNP3: 0-65532
PROFIBUS: 0-126

1
(126 for
PROFIBUS)

Device network address

Baud rate

300 bps-115.2 kbps

9600 bps

The port baud rate

Data format

7E, 8N, 8E

8N

Data format and parity.
7E data format should not
be used with the MODBUS
RTU and DNP3 protocols