Appendix F Data Scales

The maximum values for volts, amps and power in the PowerSmart+
PQM setup and in communications are limited by the voltage and current
scale settings. See

Device Options

in Chapter 4 on how to change the

voltage and current scales in your meter.

The following table shows the meter data scales.

Table 27: Data Scales Values

Scale

Conditions

Range

Maximum voltage
(V max)

All configurations

Voltage scale × PT Ratio, V

1

Maximum current
(I max)

All configurations

Current scale × CT Ratio, A

2, 3

Wiring 4LN3, 3LN3, 3BLN3

V max × I max × 3, W

Maximum Power

4

Wiring 4LL3, 3LL3, 3BLL3,
3OP2, 3OP3, 3DIR2

V max × I max × 2, W

25, 50 or 60 Hz

100 Hz

Maximum frequency

400Hz

500 Hz

1

The default voltage scale is 144V. The recommended voltage scale is

120V+20% = 144V for using with external PT’s, and 690V+20% = 828V
for a direct connection to power line.

2

CT Ratio = CT primary current/CT secondary current

3

The default current scale is 2 × CT secondary (2.0A with 1A secondary

and 10.0A with 5A secondary).

4

Maximum power is rounded to whole kilowatts. With PT=1.0, it is

limited to 9,999,000 W.