Primary and Secondary Volts

Volts can be displayed in primary (default) or secondary units. The volts
display mode can be changed through the display setup (see

Configuring

the Display

).

Phase Power Readings

In configurations with the neutral wire, in addition to total three-phase
powers, the meter can show per-phase power readings. By default, they
are disabled. See

Configuring the Display

on how to enable per-phase

power readings in your meter.

Fundamental Component

The PowerSmart+ PQMEH can display total displacement power factor and
active power for the fundamental component if it is enabled through the
display setup (see

Configuring the Display

).

When phase power readings are allowed, the PowerSmart+ PQMEH also
displays per-phase displacement power factor and active power for the
fundamental component.

3.2 Data Displays

The PowerSmart+ PQM has 8 multi-page data displays listed in the
following table.

Data Display

Menu

Sequence

Display Label

Display Contents

1

Measurements

Present 7 Measurements Data Displays:
V, I, P, S, Q, PF, Max. DMD, MIN/MAX,
Energy and Billing/TOU

2

Harmonics

V/I individual harmonics and Harmonics
Spectrum

3

Waveforms

Vn/In Waveforms with THD value

4

Phasor

Voltage and current phasors diagram

5

Digital I/O

Status of counters, Digital IN and relays
out

6

Device Control

Diagnostics and Alarms displays

7

Basic Settings

Device configuration display

8

Device Info

Device model, identification, firmwares
version, COM1,COM2

TEST Mode Data Display

The TEST data display is shown in TEST mode in place of the billing period
data displays.

TEST mode display:
test LED pulse rate in secondary Wh/imp;
test kWh and kvarh energy readings in primary units
with an extended 0.001 kWh resolution.

TEST mode setup menu is enabled in Device
Setup/Device Options menu.