Chapter 5 Configuring the PowerSmart+ PQM

Configuring Billing/TOU

96

PowerSmart+ Power Quality Meter

Figure 5-16: Energy/TOU Setup Dialog Box – Billing/TOU Registers tab

2. Configure the register options according to the valid parameters

shown in Table 18.

Table 18: Billing/TOU Register Options

Parameter

Options

Default

Description

Billing/TOU Registers

TOU

Unchecked
Checked

Unchecked Links tariff registers to the selected energy

source

Use Profile

Unchecked
Checked

Checked

Enables recording energy registers in a daily
billing profile file (both total and tariff
registers if TOU is enabled).

Dmd Profile

Unchecked
Checked

Unchecked Enables recording maximum demand

registers in a daily billing profile file (both
total and tariff registers if TOU is enabled)

Sum Profile

Unchecked
Checked

Checked

Enables recording total (summary) registers
in a daily billing profile file.

Units

kWh, kvarh, kVAh,

m3, CF (cubic
foot), CCF
(hundred cubic
feet)

None

The register measurement units. When a
register is linked to an internal energy
source, it is set automatically. When an
external pulse source is used, the user can
select a measurement unit for the register.

Register Source List

Source Input

None
kWh Import
kWh Export
kvarh Import
kvarh Export
kVAh,
DI1-DI12

None

Links an energy source to the register

Multiplier

0.001 to 100.000

1.000

The multiplication factor for the energy
source. Unchangeable for internal energy
sources.

Target

Reg#1- Reg#4

None

Defines the target billing register for the
energy source. It is set automatically.