Energy pulse led, Port activity leds – E-Mon E-PS-E-RTU-N User Manual

Page 57

Advertising
background image

Chapter 3 Using Front Display

Display Operations

PowerSmart+ Power Quality Meter

57

Energy Pulse LED

The PowerSmart+ has a red “Energy Pulse” LED for calibration. It flashes
at a constant rate when a load is applied to the meter.

There are two modes of LED operation:

NORMAL mode: the LED pulses indicate imported Wh at a rate

of 1,000 pulses per kWh

TEST mode: the LED pulses indicate either imported Wh, or

imported (inductive) varh at a rate of 10,000 pulses per
kWh/kvarh

The energy test mode can be enabled through the

Device Options

setup.

When in test mode, the energy and demand accumulators do not account
for consumed energy.

Port Activity LEDs

The meter has two green LEDs “RX” and “TX”, which indicate activity on
the COM1 communication port. The LEDs flash when the port is receiving
or transmitting data.

Advertising
This manual is related to the following products: