Chapter 5 Configuring the PowerSmart+ PQM

General Meter Setup

PowerSmart+ Power Quality Meter

83

Configuring Analog Outputs

The meter can be ordered with two optional analog outputs with options
for 0-1mA, ±1mA, 0-20mA and 4-20mA current outputs.

Using Power Software

Select General Setup from the Meter Setup menu, and then click on the
Analog Outputs tab.

Figure 5-10: General Setup Dialog Box – Analog Outputs Tab

The available analog output options are described in Table 13.

Table 13: Analog Output Options

Option

Range

Description

AO type

0-1mA
±1mA
0-20mA
4-20mA

The analog output type. When connected to the
meter, shows the actual AO type received from
the device. When working off-line, select the
analog output option corresponding to your
analog module.

Output
parameter

See Appendix B Selects the measured parameter to be

transmitted through the analog output channel.

Zero scale

Defines the low engineering scale (in primary
units) for the analog output corresponding to a
lowest (zero) output current (0 or 4 mA)

Full scale

Defines the high engineering scale (in primary
units) for the analog output corresponding to a
highest output current (1 or 20 mA)

When you select an output parameter for the analog output channel, the
default engineering scales are set automatically. They correspond to the
maximum available scales. If the parameter actually covers a lower range,
you can change the scales to provide a better resolution on an analog
output.