Configuring dnp3, Dnp options – E-Mon E-PS-E-RTU-N User Manual

Page 105

Advertising
background image

Chapter 5 Configuring the PowerSmart+ PQM

Configuring Communication Protocols

PowerSmart+ Power Quality Meter

105

The 32-bit Modbus registers are factory-set to integer format. To change
the register format:

1. Select Protocol Setup from the Meter Setup menu, and click on

the Modbus Registers tab.

2. Change the 32-bit register format in the Modbus Options pane.

3. Click Send to download your setup to the meter.

Configuring DNP3

Refer to the PowerSmart+ PQM DNP3 Reference guide for information on
the DNP3 protocol implementation and a list of the available data points.

DNP Options

Select Protocol Setup from the Meter Setup menu and click on the
DNP Options tab.

Figure 5-22: Protocol Setup Dialog Box – DNP Options Tab

The following table describes available options. Refer to the DNP3 Data
Object Library document available from the DNP User’s Group on the
DNP3 object types.

Table 19: DNP Options

Parameter

Options

Default

Description

Binary Inputs (BI)

Binary Input Object

Single-bit
With Status

Single-bit

The default BI object variation for
requests with qualifier code 06 when no
specific variation is requested

Analog Inputs (AI)

Analog Input Object

32-bit
32-bit–Flag
16-bit
16-bit–Flag

16-bit-Flag

The default AI object variation for
requests with qualifier code 06 when no
specific variation is requested