Chapter 5 Configuring the PowerSmart+ PQM

General Meter Setup

PowerSmart+ Power Quality Meter

87

Using Power Software

Select General Setup from the Meter Setup menu, and then click on the
Control/Alarm Setpoints tab.

The following table lists the available setpoint options.

Table 15: Setpoint Options

Option

Range

Description

Trigger parameter

See Appendix C

The trigger parameter that is used as an
argument in the logical expression

Operate limit

The threshold (in primary units) at which the
conditional expression would be evaluated to
true. Not applicable for digital triggers.

Release limit

The threshold (in primary units) at which the
conditional expression would be evaluated to
false. Defines the hysteresis for analog
triggers. Not applicable for digital triggers.

Operate delay

0.1-999.9 sec

The time delay before operation when the
operate conditions are fulfilled

Release delay

0.1-999.9 sec

The time delay before release when the
release conditions are fulfilled

Action

See Appendix C

The action performed when the setpoint
expression is evaluated to true (the setpoint
is in operated state)

Figure 5-12: General Setup Dialog Box – Control/Alarm Setpoints Tab

Using Numeric Triggers

For numeric (analog) triggers, you can specify two thresholds for each
trigger to provide hysteresis (dead band) for setpoint operations.

The Operate Limit defines the operating threshold, and the second
Release Limit defines the release threshold for the trigger. The trigger
thresholds are specified in primary units.