Chapter 5 Configuring the PowerSmart+ PQM

General Meter Setup

76

PowerSmart+ Power Quality Meter

Parameter

Options

Default

Description

Volt/Ampere
Demand Period

0-1800 sec

900 sec

The length of the demand period
for ampere and volt demand
calculations

1. Always specify the wiring mode and transformer ratings prior to
setting up setpoints and analog outputs.

2. The maximum value for the product of the phase CT primary
current and PT ratio is 57,500,000. If the product is greater, power
readings are zeroed.

Figure 5-6: General Setup Dialog Box – Basic Setup Tab

Table 9 lists the available wiring modes.

Table 9: Wiring Modes

Wiring Mode

Description

3OP2

3-wire Open Delta using 2 CTs (2 element)

4LN3

4-wire Wye using 3 PTs (3 element), line-to-neutral voltage readings

3DIR2

3-wire Delta Direct Connection using 2 CTs (2 element)

4LL3

4-wire Wye using 3 PTs (3 element), line-to-line voltage readings

3OP3

3-wire Open Delta using 3 CTs (2½ element)

3LN3

4-wire Wye using 2 PTs (2½ element), line-to-neutral voltage
readings

3LL3

4-wire Wye using 2 PTs (2½ element), line-to-line voltage readings

3BLN3

3-wire Broken Delta using 2 PTs, 3 CTs (2½ element), line-to-neutral
voltage readings

3BLL3

3-wire Broken Delta using 2 PTs, 3 CTs (2½ element), line-to-line
voltage readings