Configuring alarm/control setpoints, Using power software – E-Mon E-PS-E-RTU-N User Manual

Page 85

Advertising
background image

Chapter 5 Configuring the PowerSmart+ PQM

General Meter Setup

PowerSmart+ Power Quality Meter

85

Using Power Software

Select General Setup from the Meter Setup menu, and then click on the
Pulse/Event Counters tab.

Table 14 lists available counter options.

Table 14: Counter Options

Option

Range

Default

Description

Pulse Input

None,
DIGITAL INPUT #1 - #12

None

Links a digital input
to the counter

Multiplier

1-9999

1

The value added to
the counter when a
pulse is detected on
the pulse source
input

Counter Value

Displays the present
counter contents

Figure 5-11: General Setup Dialog Box – Pulse/Event Counters

You can preset a counter to a required value or clear it without affecting
the counter setup.

To preset or clear a counter:

1. Click the Online button on the Power Software toolbar before

accessing the setup dialog box.

2. Type in the required value into the Counter Value field.

3. Click Send

Configuring Alarm/Control Setpoints

The PowerSmart+ PQM has an embedded logical controller that can
perform different actions in response to user-defined internal and external
events. Unlike a PLC, the meter uses a simplified programming technique
based on setpoints that allows the user to define a logical expression