Chapter 3 Using Front Display

Display Operations

PowerSmart+ Power Quality Meter

41

Direct active power flow – delivered active energy.

Reversed active power flow – received active energy.

Phase Presence Indicators

Phase presence indicators “123” show the status of either V1-V2-V3
phase-to-neutral voltages in line-to-neutral wiring modes, or V12-V23-
V31 phase-to-phase voltages in line-to-line wiring modes.

Indicator

Icon

Description

123

All voltages are present and above the voltage dip threshold.

1 3

123

Blinking phase indicator – the phase voltage is below the
defined voltage dip threshold. Possibly indicates an incorrect
meter nominal voltage setting (see

Basic Meter Setup

in

Chapter 5).

1–3

Dashed phase indicator - the phase voltage is either missing or
below the voltage interruption threshold.

If the phase voltage is below the defined voltage dip threshold, its
corresponding phase indicator is blinking.

If the phase voltage is either missing or below the voltage interruption
threshold, the phase indicator is replaced with a dash

Display Features

While energizing the device the display will show an init screen followed
by phase-voltages measurements as described below:

The PowerSmart+ PQM display has a number of programmable features
that can be disabled, enabled and adjusted via the meter Display Setup
(see

Display Setup

in Chapter 5).

Backlight

A short press on any button while the display backlight is off switches the
backlight on.

The backlight stays on as long as you selected in the display setup and
then dims to conserve power. The backlight time is factory set to 1 minute
and can be programmed from 1 to 10 minutes. You can temporarily set
the backlight to continuous operation if you need to work in dark for more
time.

Contrast

The contrast can be adjusted via the meter Display Setup (see

Display Setup

in Chapter 5).

Auto-Return

If the Auto-Return feature is enabled and no button is pressed for the
programmable Auto-Return interval (1 to 30 minutes for data displays;
fixed at 5 minutes for setup menus), the display automatically returns to
the default page from any other data display or a setup menu.