background image

Chapter 2 Installation

I/O Connections

32

PowerSmart+ Power Quality Meter

4AO Module - Analog Outputs

The 4AO module has four optically isolated analog outputs with an internal
power supply and current output options of 0-20 mA and 4-20 mA
(current loop load of up to 500 Ohm), 0-1 mA and ±1 mA (2mA 100%
overload, current loop load of up to 5 kOhm).

Figure 2-24: Analog Output Connection

It is recommended to connect unused Analog output
channels to Common terminal.

The 4AO module TERMINAL is for use only with equipment

which has no live parts which are ACCESSIBLE

The RATING of the insulation of the external equipment for

use with the 4AO module, shall comply according to
Installation Category II for insulation to be suitable for
SINGLE FAULT CONDITION

The external equipment TERMINAL connection type is

normally terminal block for wire size 14 AWG (up to 1.5
mm2)

The type of equipment that might be connected to the

TERMINAL is:

Programmable Logic Controller for automation – PLC

Digital or Analog meter