Setting up ethernet, Using the front display, Using power software – E-Mon E-PS-E-RTU-N User Manual

Page 69

Advertising
background image

Chapter 5 Configuring the PowerSmart+ PQM

Configuring Communications

PowerSmart+ Power Quality Meter

69

Parameter

Options

Default

Description

Response delay 0-1000 ms

5 ms

The minimum time after
the last request character
is received to start the
transmission.

NOTES:

1. The meter provides the permanent MODBUS TCP server on port

502.

2. Selecting the DNP3 protocol launches the second DNP3 TCP server

in addition to the MODBUS server allowing simultaneous
connections on both ports. Selecting the MODBUS protocol
disables the DNP3 TCP server.

3. When you change the COM2 settings through the Ethernet port,

the device port restarts so communications will be temporarily
lost. You may need to wait some additional time until Power
Software restores a connection with your device.

Setting Up Ethernet

Using the Front Display

Select Network Setup from the Device Setup menu. This menu entry
appears only if the optional Ethernet module is plugged into the
meter. It allows you to set up the meter network address and the default
gateway.

See

Viewing and Changing Setup Options

in Chapter 3 for information on

configuring parameters via the front display.

Using Power Software

Select Communications Setup from the Meter Setup menu, and then
click on the Network Setup tab.

Advertising