A.12 measurement specifications – E-Mon E-PS-E-RTU-N User Manual

Page 140

Advertising
background image

Appendix A Technical Specifications

140

PowerSmart+ Power Quality Meter

A.12 Measurement Specifications

Table 21: Measurement Specifications Parameters

Accuracy

Parameter

Full Scale @ Input

Range

%

Reading

% FS

Conditions

Range

Voltage

120VxPT @ 120V
400VxPT @ 690V

0.2

0.02

10% to 120% FS 0 to 1,150,000 V

Starting voltage
1.5-5.0% FS (selectable)

Line current

CT

0.2

0.02

For In = 5A
1% to 200% FS
For In = 1A
5% to 200% FS

0 to 50,000 A
Starting current 0.1% FS

Active power

0.36×PT×CT @ 120V
1.2×PT×CT @ 690V

0.3

0.02

|PF| ≥ 0.5

1

-10,000,000 kW to
+10,000,000 kW

Reactive power

0.36×PT×CT@ 120V
1.2×PT×CT @ 690V

0.3

0.04

|PF| ≤ 0.9

1

-10,000,000 kvar to
+10,000,000 kvar

Apparent power

0.36×PT×CT @ 120V
1.2×PT×CT @ 690V

0.3

0.02

|PF| ≥ 0.5

1

0 to 10,000,000 kVA

Power factor

1.000

0.2

|PF| ≥ 0.5,
I ≥ 2% FSI

-0.999 to +1.000

Frequency

50 Hz
60 Hz
25 Hz
400 Hz

0.02
0.04

V

L-N

> 25V

15 Hz to 70 Hz
15 Hz to 70 Hz
15 Hz to 70 Hz
320 Hz to 480 Hz

Total Harmonic
Distortion, THD
V (I), %Vf (%If)

999.9

1.5

0.2

THD ≥ 1%,
V ≥ 10% FSV and

V

L-N

> 25V,

I ≥ 10% FSI

0 to 999.9

Total Demand
Distortion, TDD,
%

100

1.5

TDD ≥ 1%,
I ≥ 10% FSI,

V

L-N

> 25V

0 to 100

Active energy
Import & Export

Class 0.5S under conditions as per
IEC 62053-22:2003

0 to 999,999,999 kWh

Reactive energy
Import & Export

Class 0.5S under conditions as per
IEC 62053-22:2003, |PF| ≤ 0.9

0 to 999,999,999 kvarh

Apparent energy

Class 0.5S under conditions as per
IEC 62053-22:2003

0 to 999,999,999 kVAh

PT - external potential transformer ratio

CT - primary current rating of the external current transformer

FSV - voltage full scale

FSI - current full scale

Vf

- fundamental voltage

If

- fundamental current

NOTES

1. Accuracy is expressed as ± (percentage of reading + percentage of full

scale) ± 1 digit. This does not include inaccuracies introduced by the
user's potential and current transformers. Accuracy calculated at
1second average.

2. Specifications assume: voltage and current waveforms with THD ≤ 5% for

kvar, kVA and PF, and reference operating temperature 20°C - 26°C.

3. Measurement error is typically less than the maximum error indicated.

1

@ 80% to 120% of voltage FS, 1% to 200% of current FS and frequency 50/60 Hz